HYDROTHERM ENGINEERING SERVICES
Auto Tank Gauging System

Auto Tank Gauging System

Send Inquiry

Model 924B Specifications

•Power Requirements: Nominal 12+ VDC from I.S. Barrier

•Operating Temperature: -40°F to 158°F (-40°C to +70°C)

•Maximum Total-Run Wiring Length*: 1,000 feet (305 m) Belden 88760 or Alpha 55371

•500 feet (152 m) Belden 88761 (or equivalent)

•Level Measurement Product: +/-0.00005 inches (+/- 0.0127 cm)

•Water: +/-0.04 inches (+/- 1 mm)

•Temp. Resolution/Accuracy:+/- 0.1°C, +/-0.5°C

•Classifications: Class I, Division 1, Group D

•Certifications: IECEx UL 11.0012X

•DEMKO 11 ATEX 1012670X

•I.S. Barrier Used: 12V ONLY

•Multi-drop Restriction**: 924B is the only probe that can be multi-dropped at a maximum of four (4) probes per channel